الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين Water Treatment Units Work Operation and Maintenance EQUIPMENT: Water Treatment Units Daily Routine work 1. Check and record: Reading in the instruments 2. Check chemical levels in drum Weekly Routine work 1. Strainer cleaning 2. Re-adjust metering pumps and […]
Operation
الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين ELECTRIC BOILERS Work Operation and Maintenance Daily Routine Work 1. Check desired pressure, temperature and current in boiler system as per log sheet 2. Check all valves for free travel and packing leak 3. Check conductivity of treated water […]
الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين Fan Coil Units F.C.U. Work Operation and Maintenance Equipment: Fan Coil Units F.C.U. Daily Routine Work Check and Record 1. Check undue noise or vibration and any evidence of water leakage 2. Check condensate drain line for blockage 2W.Routine […]
الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين AIR HANDLING UNITS Work Operation and Maintenance EQUIPMENT : AIR HANDLING UNITS Daily Routine Work 1. Check & Record: Inlet and outlet temperature and pressure of chilled water air temperature: re-circulation and flow, room thermostat setting, Motor: voltage and […]
الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين PUMPS Work Operation and Maintenance EQUIPMENT: – PUMPS Daily Routine Work 1. Check and Record Suction and discharge pressures, Motor voltage and current water flow rate 2. Check: gland leakage, Motor temperature by feeling with hand 3. Inspect for […]
الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين D.X. Units Air Conditioners Work Operation and Maintenance D.X. means direct expansion Check and Record A) Before Operation season routine work 1. Inspection of automatic devices 2. Inspection and maintenance of electric devices “motors, magnetic switches …etc 3. Inspection […]
الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين COOLING TOWERS During shut down season Work Operation and Maintenance Check and Record During shut down season 1. Drain cooling tower sump and clean basin 2. Change gearbox oil 3. Clean cooling towers and sump, inspect and repair as […]
الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين COOLING TOWERS Monthly Routine Work Operation and Maintenance Check and Record 1. Check and clear salt buildup on fan blades, gearbox body and fan 2. Check electrical connections of motors Guards 3. Check pulleys & belt tension; adjust if […]