Chillers Monthly Routine work Operation and Maintenance
Check and Record
1. Oil filter cleaning oil pump function and current
2. Purge Unit filter cleaning. For under pressure refrigerants
3. Check: Relief Valves, rupture discs for leaks
4. Test: Operation and safety cutouts, automatic controls and
automatic devices for correct operation
5. Test: all gauges for correct reading – calibrate if necessary
6. Visually inspect capillary tubes for pinching or damage for
thermostat and pressure switches
Lubricate: as recommended by Manufacturer
1. Vane Linkage
2. Motor Assembly
3. Air compressor if there is pneumatic control
4. Inspect and clean the electrical panels and electrical connections
5. Top-up thermometer pockets with oil
في أمان الله