الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين
DUCT WORKS Selection Tips DETAILED TECHNICAL SPECIFICATION
A. All ducting must be made of galvanized steel sheet to ASTM A525
lock-forming quality, having zinc coating of 275gm/M² for both sides
in accordance with ASTM A90 and of tensile strength 28/33 tons per square inch
B. All ducting must be made as indicated in the installation drawings and
successful tenderer must check the installation and building before
hand and ensure that the existing structures, etc., must not come in
the way of ducting at time of installation
Dimensions of ducting can be altered by the contractor with the prior
approval of concerned Engineer without altering permissible airflow rates
C. All ducting must be suitably stiffened to avoid vibration, sagging and
running effects due to airflow. All ducting must be made airtight
D. Gauges of G.I sheeting, type of joints, bracing, etc., used for the
manufacture ducting must be as shown below
E. The throat radius of bend must not exceed half the width of associated
side of the duct and where it is not possible to comply with this duct turning
vane must be used along with the right angle bends
The duct turning vanes must be spaced in such a way that the speed
ratio of each of the individual elbows must be around 6:1
Maximum Side inches US Standard Gauge
Transverse Joints and Bracing 154BUp to 12″ 24
¾” pocket or slip joint at 8 ft. centres 13 – 18” 24
1” pocket joint at 4 Ft. centers with cross breaking 19 – 30” 22
1” pocket joint at 4 Ft. centers with cross breaking 31 – 42” 22
1½” pocket joint at 4 Ft. centers with cross breaking and ½ x ½ x 1/8
angle with girth at 8 ft. centres bolted to the pocket joint 43 – 54” 20
1½” pocket joint at 4 Ft. centers with cross breaking and 1½ x 1½ x 3/16
angle with girth at 8 ft. centres bolted to the pocket joints 55 – 72” 20
1½” pocket joint at 4 Ft. centers with cross breaking and 1½ x 1½ x 3/16
angle with girth at 4 ft. centres bolted to the pocket joints 73 to Up 18
2½” x 1½” x 3/16 angles at 4 Ft. centers bolted to the duct with 3/8
bolts at 1½ centers and fastened together with 3/8” bolts at 2 centres
with rubber gasket between the 2 angles and cross breaking
Joints
50 mm Slip Joint or Draw Band is acceptable through 1500 mm size
Slip or Draw Band Joint Flanged Joint
All tees, Bends and Elbows must be constructed with radius
of not less than 1½ times diameter of duct on centerline
Where not possible and where rectangular elbows are used
aerofoil-turning vanes must be provided
Transformation of duct sizes must be gradual, not exceeding
15 degrees divergence and 30 degrees convergence
Round duct fittings must be of welded type construction
For ducts of diameter up to and including 300-mm. diameter
one-piece smooth 90 deg. elbows must be used. Over 300-mm dia
they must be 5 piece welded
Turning Vanes
must be fabricated in accordance with SMACNA Standards
Turning vanes must be as follows
Factory or site-fabricated using factory-fabricated vane spacing rails
Turning vanes must be provided in all square elbows, take-off or
extension collars to supply outlets and tap-in branch take-off connections
Turning vanes must be reinforced by rods or of sectional construction
Turning vane arrangements and thickness must be as shown
153 B SINGLE 152 B VANE 151 B SCHEDULE Type Space between Vanes
Radius Gauge Small Large
1½” 3” 2” 4½” 24 22
Volume Control Damper
Volume control dampers must be provided in ductwork to regulate and
balance air systems, since dampers on the air inlet and outlet must be
used only for fine secondary regulating or balancing
The damper must be fabricated in accordance with
SMACNA Duct Construction Standards
Single blade dampers must be used for damper widths up to 300 mm
provided that there is sufficient length of straight duct after the
damper to ensure equal flow before the next take-off or outlet
Where the damper width is over 300 mm. multi -blade dampers must be used
Multi blade dampers styles must be generally parallel blade for two-position
operation and opposed blades for modulating position
The blades must be constructed of galvanized sheet, suitably
stiffened by forming or other method, and assembled in prime coated
or galvanized channel frame with suitable hardware
The bearings must be of bronze or oil impregnated nylon
Looking and indicating quadrant regulator must be provided for each damper
The indicating quadrant must be clearly marked to indicate
close, ¼, ½ , ¾ and open positions
On insulated ducts, quadrant regulators must be mounted
on stand off mounting brackets or bases
For motor operated damper, the motor-operator must be electric type
Fire Dampers
must be fabricated in accordance with NFPA 90A
and UL 555 or equivalent and must be
1• To be provided in ducts and openings in shafts, floor
firewalls, fire partitions and the rated ceilings
2• In horizontal ducts, fire dampers may be single or of a multi
blade type. In vertical ducts only single blade type must be used
3• Galvanized sheet metal housing to be provided with angle flanges on both sides
4• The damper must be of 1.6 mm thick sheet steel or steel/mineral
fiber/steel sandwich of equivalent fire resistance, thermally released
5• Fire dampers must be equipped with fuse plug, positioning levers
fittings and position indicator accessible from outside
Grilles and Registers
They must be furnished with sponge rubber gaskets or foam
tape behind the frame to eliminate air leakage and with nylon
bushings or PVC at the blades connection to the frame to eliminate
corrosion and vibration. Free cross-sectional area must be at least 65 percent
1- Supply air registers and grilles must have individually adjustable
horizontal front blades and vertical rear blades
2- Supply air register must be equipped with key
operated, opposed blade volume control damper
3- Return and exhaust air registers and grilles must have
fixed single deflection blades set at an angle of 35 degrees
4- Return and exhaust air registers must be equipped with
key operated, opposed blade volume control damper
5- All opposed blade volume control dampers must be polyester
powder coated ovens taken with black colour finish
Jet Diffusers
must have manual discharge pattern adjustment from the
front or back of diffuser, the outer flange of the jet diffuser
to be made of aluminium, the inner core and rings to be made
of mild steel construction, to be coloured by
electrostatic polyester powder coating finish
Access Doors
Airtight access doors with rubber linings must be installed in all ducts
at fans, filters, heaters, fire dampers and volume dampers for inspection
cleaning and maintenance purposes
The opening in the ductwork must be properly stiffened at the edges
with frames riveted or welded to the duct
The access door must be
All Access Doors mounted on insulated ducts must be
of sandwich type, having the same insulation thickness
as that of the duct, with Cam Lock handles
Maximum Size(mm) No. of Hinges No. of Handles Door Gauge Back Frame
12” x 12” 2 1 26 26 24 16” x 20” 2 2 24 26 22 24” x 24” 3 2 22 26 22
Flexible Connections
Flexible connections must be fitted on all suction and discharge
connections of fans and air conditioning units, for preventing
transmission of vibration through the ducts to occupied spaces
Flexible connections must be made from flame proof, factory
fabricated from chemically impregnated canvas
Connections must fit closely and be secured in an airtight
fashion to duct work, fans and apparatus by means of angle
iron or flat iron frames. The unclamped section of the flexible
connection between the apparatus and the ductwork must be
not less than 150 mm. in length. Flexible connections must not be painted
Supports and Hangers
Installation of supports and hangers must be
Supports and hangers must be attached only to structural
framing members and concrete slabs. They must not be anchored
to metal decking unless a means is provided and approved for
preventing the anchor from puncturing the metal decking
Supports must generally be made from galvanized steel sections
and where heavy items of equipment occur within ductwork
additional support must be provided as necessary
Duct work hung from inserts or from clip angles must
be secured with expansion bolts in shear.
Supports for horizontal ducts must be
RECTANGULAR DUCT Length of Longer Side (mm) Drop Rod Diameter (mm)
Bearing Member (mm) 155BMaximum Spacing ( inch) 156 B up to 12” 8
20 x 3 Flat 120” 157B Over 12” up to 24” 8 25 x 25 x 3 angle 120”
Over 24” up to 40” 10 40 x 40 x 4 angle 100” Over 45” up to 64” 10
50 x 50 x 5 angle 100” Over 64” 15 75 x 75 x 6 angle 100”
Design of supports for vertical ducts will be dictated by site
conditions and spacing may be greater than for horizontal ducts
Supports for vertical ducts must be angles and
channels made of galvanized or painted black steel
Vertical duct must be fastened with a minimum
of 2 supports at each floor
في أمان الله