COOLING TOWERS During shut down season Work Operation and Maintenance

[​IMG]

[​IMG]

الحمد لله والصلاة والسلام على رسول الله وعلى آله وصحبه أجمعين

COOLING TOWERS During shut down season Work Operation and Maintenance

[​IMG]

Check and Record

During shut down season

1. Drain cooling tower sump and clean basin
2. Change gearbox oil
3. Clean cooling towers and sump, inspect and repair as necessary: woodwork
plastic work, valves, spray nozzles, fans, pipe work and repair any cracks in the basin
4. Paint woodwork if applicable, with suitable preservative
5. Check and adjust fan blade pitch angle of the cooling tower, if applicable
6. Check bearing and change if necessary
7. Remove and clean eliminators and fills
8. Overhaul all valves and lubricate spindles
9. Check bearing bolts, fan anti-vibration mountings, tighten or replace if necessary
10. Inspect, repair or replace as necessary all electrical works
11. Inspect all cooling tower inlet louvers and replace if necessary
12. Clean fan guard and cover; check cover for tightness and paint
13. Paint the cooling tower
14. Inspect fill tile for foreign debris
15. Check motors and starters
16. Check alignment of fan shaft coupling
17. Insulation test for all electrical motors
18. Change screen in basin if necessary

Note: The work should also include any other routines recommended by manufacturer